| Model | CT180 | CT200 | CT300 | CT400 | CT500 | CT600 |
| Rated Capacity | 180kVA/180kW | 200kVA/200kW | 300kVA/300kW | 400kVA/400kW | 500kVA/500kW | 600kVA/600kW |
| Number of Power Modules Installed | 6 | 4 | 6 | 8 | 10 | 12 |
| Rated Capacity of Power Modules | 30kVA/30kW | 50kVA/50kW | 50kVA/50kW | 50kVA/50kW | 50kVA/50kW | 50kVA/50kW |
| Input | Phase Count | Three-phase five-wire (3Ph+N+PE) | Three-phase five-wire (3Ph+N+PE) | Three-phase five-wire (3Ph+N+PE) | Three-phase five-wire (3Ph+N+PE) | Three-phase five-wire (3Ph+N+PE) |
| Rated Input Voltage | 380Vac/400Vac/415Vac | 380Vac/400Vac/415Vac | 380Vac/400Vac/415Vac | 380Vac/400Vac/415Vac | 380Vac/400Vac/415Vac | 380Vac/400Vac/415Vac |
| Input Voltage Range | 305~485Vac (no derating); 138~305Vac (linearly derating between 40%-100% load) | 305~485Vac (no derating); 138~305Vac (linearly derating between 40%-100% load) | 305~485Vac (no derating); 138~305Vac (linearly derating between 40%-100% load) | 305~485Vac (no derating); 138~305Vac (linearly derating between 40%-100% load) | 305~485Vac (no derating); 138~305Vac (linearly derating between 40%-100% load) | 305~485Vac (no derating); 138~305Vac (linearly derating between 40%-100% load) |
| Input Frequency Range | 40-70Hz | 40-70Hz | 40-70Hz | 40-70Hz | 40-70Hz | 40-70Hz |
| Input Power Factor | ≥0.99 | ≥0.99 | ≥0.99 | ≥0.99 | ≥0.99 | ≥0.99 |
| Input Current Harmonics | ≤3% | ≤3% | ≤3% | ≤3% | ≤3% | ≤3% |
| Bypass Input Voltage Range | -60% to +25% (adjustable) | -60% to +25% (adjustable) | -60% to +25% (adjustable) | -60% to +25% (adjustable) | -60% to +25% (adjustable) | -60% to +25% (adjustable) |
| Battery Voltage | Lead-acid: ±240VDC (±180VDC to ±276VDC adjustable), 12V batteries 40 (even number 30-46 adjustable) | Lithium: ±256VDC (±192VDC to ±256VDC adjustable), 3.2V cells 160 (120, 128, 150, 160 adjustable) | ||||
| Output | Phase Count | Three-phase five-wire (3Ph+N+PE) | Three-phase five-wire (3Ph+N+PE) | Three-phase five-wire (3Ph+N+PE) | Three-phase five-wire (3Ph+N+PE) | Three-phase five-wire (3Ph+N+PE) |
| Rated Output Voltage | 380Vac/400Vac/415Vac | 380Vac/400Vac/415Vac | 380Vac/400Vac/415Vac | 380Vac/400Vac/415Vac | 380Vac/400Vac/415Vac | 380Vac/400Vac/415Vac |
| Output Voltage Regulation | ±1% | ±1% | ±1% | ±1% | ±1% | ±1% |
| Output Frequency Precision | Utility mode: tracks bypass input; Battery mode: 50Hz/60Hz ±0.1% | Utility mode: tracks bypass input; Battery mode: 50Hz/60Hz ±0.1% | Utility mode: tracks bypass input; Battery mode: 50Hz/60Hz ±0.1% | Utility mode: tracks bypass input; Battery mode: 50Hz/60Hz ±0.1% | Utility mode: tracks bypass input; Battery mode: 50Hz/60Hz ±0.1% | |
| Output Power Factor | 1 | 1 | 1 | 1 | 1 | 1 |
| Output Waveform Distortion | ≤1% (linear load) ≤4% (non-linear load) | ≤2% (linear load); ≤5% (non-linear load) | ≤2% (linear load); ≤5% (non-linear load) | ≤2% (linear load); ≤5% (non-linear load) | ≤2% (linear load); ≤5% (non-linear load) | ≤2% (linear load); ≤5% (non-linear load) |
| Output Current Peak Ratio | 3:01 | 3:01 | 3:01 | 3:01 | 3:01 | 3:01 |
| Overload Capability | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 0.2 seconds | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 0.2 seconds | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 0.2 seconds | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 0.2 seconds | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 0.2 seconds | 105%-110%: 60 minutes; 110%-125%: 10 minutes; 125%-150%: 1 minute; >150%: 0.2 seconds |
| System Efficiency | Online mode: 97%, ECO mode: 99% | Online mode: 97%, ECO mode: 99% | Online mode: 97%, ECO mode: 99% | Online mode: 97%, ECO mode: 99% | Online mode: 97%, ECO mode: 99% | Online mode: 97%, ECO mode: 99% |
| Switching Time | 0ms | 0ms | 0ms | 0ms | 0ms | 0ms |
| Maximum Number of Parallel Units | 6 units | 6 units | 6 units | 6 units | 6 units | 6 units |
| Protection Features | Output short circuit protection, output overload protection, over-temperature protection, battery low voltage protection, output under-voltage protection, fan fault protection, etc. | Output short circuit protection, output overload protection, over-temperature protection, battery low voltage protection, output under-voltage protection, fan fault protection, etc. | Output short circuit protection, output overload protection, over-temperature protection, battery low voltage protection, output under-voltage protection, fan fault protection, etc. | Output short circuit protection, output overload protection, over-temperature protection, battery low voltage protection, output under-voltage protection, fan fault protection, etc. | Output short circuit protection, output overload protection, over-temperature protection, battery low voltage protection, output under-voltage protection, fan fault protection, etc. | Output short circuit protection, output overload protection, over-temperature protection, battery low voltage protection, output under-voltage protection, fan fault protection, etc. |
| Communication Interfaces | Standard: RS485, CAN, NET (including SNMP functionality), dry contact interface, EPO; | Optional: WIFI module, GPRS module, battery temperature sensor, EMD environmental detector | Standard: RS485, CAN, NET (including SNMP functionality), dry contact interface, EPO; | Optional: WIFI module, GPRS module, battery temperature sensor, EMD environmental detector | Standard: RS485, CAN, NET (including SNMP functionality), dry contact interface, EPO; | Optional: WIFI module, GPRS module, battery temperature sensor, EMD environmental detector |