| Availability: | |
|---|---|
| Quantity: | |
Realize online double conversion
Output power factor 0.8
Wide AC input range (190V~520V) 50Hz inverter mode
ECO mode provides energy saving effect (ECO)
Emergency shutdown function (EPO)
Compatible with engine input
Charger capacity expanded to 8A for longer operation
SNMP+USB+RS232 multiple communications three-stage charging design to optimize battery performance
optional maintenance bypass switch
Compatible with single input
| Model | CT01031TL | CT01531TL | CT02031TL |
| Capacity | 10kVA/8kW | 15kVA/12kW | 20kVA/16kW |
| Phase | Three Phase Input, Single Phase Output | Three Phase Input, Single Phase Output | Three Phase Input, Single Phase Output |
| Input Voltage | 3 x 400VAC (3Ph+N) | 3 x 400VAC (3Ph+N) | 3 x 400VAC (3Ph+N) |
| Voltage Range | 110~300VAC@50% load; 176~300VAC@100% load | 110~300VAC@50% load; 176~300VAC@100% load | 110~300VAC@50% load; 176~300VAC@100% load |
| Frequency Range | 46~54Hz or 56~64Hz | 46~54Hz or 56~64Hz | 46~54Hz or 56~64Hz |
| Power Factor | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load |
| Output Voltage | 208*/220/230/240VAC | 208*/220/230/240VAC | 208*/220/230/240VAC |
| Voltage Regulation | ±1% | ±1% | ±1% |
| Frequency Range (Synchronization Range) | 46~54Hz or 56~64Hz | 46~54Hz or 56~64Hz | 46~54Hz or 56~64Hz |
| Overload (Utility Mode) | 100%-110%: 30 minutes; 110%-130%: 5 minutes; >130%: 1 second | 100%-110%: 15 minutes; 110%-130%: 30 seconds; >130%: 1 second | 100%-110%: 15 minutes; 110%-130%: 30 seconds; >130%: 1 second |
| Overload (Battery Mode) | 100%-110%: 3 minutes; 110%-130%: 30 seconds; >130%: Immediate | 100%-110%: 1 minute; 110%-130%: 5 seconds; >130%: Immediate | 100%-110%: 1 minute; 110%-130%: 5 seconds; >130%: Immediate |
| Harmonic Distortion | ≤3% (Linear Load); ≤5% (Non-linear Load) | ≤3% (Linear Load); ≤5% (Non-linear Load) | ≤3% (Linear Load); ≤5% (Non-linear Load) |
| Transfer Time (Utility to Battery) | 0ms | 0ms | 0ms |
| Transfer Time (Inverter to Bypass) | 0ms | 0ms | 0ms |
| Efficiency (Utility Mode) | 91% | 91% | 91% |
| Efficiency (Battery Mode) | 91% | 91% | 91% |
| Battery Model | Varies by Application | Varies by Application | Varies by Application |
| Number of Batteries | 16 | 16 | 16 |
| Dimensions (Depth x Width x Height mm) | 442 x 190 x 318 | 560 x 250 x 580 | 560 x 250 x 580 |
| Net Weight (kg) | 18.4 | 25 | 30.5 |
| Operating Environment | Humidity: 0~95%RH@0~50°C (Non-condensing) | Altitude: <1000m | Noise: <58dB@1 meter |
| Control Management | Intelligent RS-232 or USB | Supported for Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC | Support for SNMP management and network browser power management |