| Availability: | |
|---|---|
| Quantity: | |
Output isolation design, can withstand various loads
Output power factor 0.8
The circuit board is fully coated with three-proof paint, which can operate in harsh environments
Independent air duct design, effectively dissipates heat and prevents pollution from entering
Wide input voltage and frequency range
Better short-circuit protection and overload capacity
Built-in maintenance bypass switch
| Model | CT00531WTL | CT00631WTL | CT00731WTL | CT01031WTL |
| Capacity | 5000VA/4000W | 6000VA/4800W | 7500VA/6000W | 10000VA/8000W |
| Phase | Three Phase Input, Single Phase Output | Three Phase Input, Single Phase Output | Three Phase Input, Single Phase Output | Three Phase Input, Single Phase Output |
| Input Voltage Range | 286-493VAC@50% load; 320-493VAC@100% load | 286-493VAC@50% load; 320-493VAC@100% load | 286-493VAC@50% load; 320-493VAC@100% load | 286-493VAC@50% load; 320-493VAC@100% load |
| Frequency Range | 40-55Hz or 56-64Hz | 40-55Hz or 56-64Hz | 40-55Hz or 56-64Hz | 40-55Hz or 56-64Hz |
| Power Factor | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load | ≥0.99@100% load |
| Output Voltage Range | 208*/220/230VAC | 208*/220/230VAC | 208*/220/230VAC | 208*/220/230VAC |
| Voltage Regulation | ±1% | ±1% | ±1% | ±1% |
| Frequency Range (Synchronization Range) | 45-55Hz or 56-64Hz | 45-55Hz or 56-64Hz | 45-55Hz or 56-64Hz | 45-55Hz or 56-64Hz |
| Overload (Utility Mode) | 110%-120%: 30 minutes; 120%-130%: 5 minutes; >130%: 1 second | 110%-120%: 30 minutes; 120%-130%: 5 minutes; >130%: 1 second | 110%-120%: 30 minutes; 120%-130%: 5 minutes; >130%: 1 second | 110%-120%: 30 minutes; 120%-130%: 5 minutes; >130%: 1 second |
| Overload (Battery Mode) | 110%-120%: 3 minutes; 120%-130%: 1 minute; >130%: 1 second | 110%-120%: 3 minutes; 120%-130%: 1 minute; >130%: 1 second | 110%-120%: 3 minutes; 120%-130%: 1 minute; >130%: 1 second | 110%-120%: 3 minutes; 120%-130%: 1 minute; >130%: 1 second |
| Harmonic Distortion | <3% (Linear Load); <5% (Non-linear Load) | <3% (Linear Load); <5% (Non-linear Load) | <3% (Linear Load); <5% (Non-linear Load) | <3% (Linear Load); <5% (Non-linear Load) |
| Transfer Time (Utility to Battery) | 0ms | 0ms | 0ms | 0ms |
| Transfer Time (Inverter to Bypass) | 0ms | 0ms | 0ms | 0ms |
| Transfer Time (Inverter to ECO) | ≤10ms | ≤10ms | ≤10ms | ≤10ms |
| Efficiency (Utility Mode) | 88% | 88% | 88% | 88% |
| Efficiency (Battery Mode) | 92% | 92% | 92% | 92% |
| Battery Model | Varies by Application | Varies by Application | Varies by Application | Varies by Application |
| Number of Batteries | 16/18 | 16/18 | 16/18 | 16/18 |
| Dimensions (Depth x Width x Height mm) | 562 x 300 x 830 | 562 x 300 x 830 | 107 x 300 x 1000 | 115 x 600 x 1200 |
| Net Weight (kg) | 84 | 107 | 107 | 115 |
| Operating Environment | Humidity: 0~95%RH@0~50°C (Non-condensing) | Altitude: <1000m | Noise: <60dB@1 meter | Humidity: 0~95%RH@0~50°C (Non-condensing) |
| Control Management | Support for Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, and MAC | Support for SNMP management and network browser power management |